Description

The AQ1000TP2 thermostat is used to control the ambient air temperature or floor temperature in hydronic heating applications. It communicates with and is powered by an AQ2000 series zoning module to provide zoning control.

Product Features:

  • 2-wire polarity-insensitive programmable network communicating thermostat
  • Liquid crystal display, with 7 user buttons for programming
  • Floor temperature sensing with minimum and maximum limits (when used with optional AQ12C20 Slab/Floor Sensor – sold separately)
  • 7-day programmable
  • Single-stage Heating and Cooling
  • Outdoor, indoor, and floor temperature display
  • Selectable temporary and permanent backlit

Product Specifications:

  • : Programmable Heat/Cool Thermostat
  • Application: Hydronic single-stage zoning, heating and cooling
  • Type: 2-wire Communicating Thermostat
  • Type of Control Provided: Proportional Integral (PI)
  • Network Zoning: Yes
  • Network Bus: Low voltage, Class II, 2-wire polarity-insensitive, digital communicating link to AQ2000 series zoning modules.
  • Zones: Single or Multi-zone
  • Power Method: Powered (24 Vdc) by AQ zoning module
  • Programmability: 7 Day Programmability
  • User Interface (Programming): LCD Display and 7 user programming buttons
  • User Interface (System Configuration):DIP Switches
  • LCD Icons Displayed (Mode):Heat on
  • LCD Icons Displayed (Mode):Comfort/Unoccupied
  • LCD Icons Displayed (Mode): Keypad Lock
  • LCD Icons Displayed (Mode):Setpoint
  • LCD Icons Displayed (Mode):Cool On
  • LCD Icons Displayed (Mode): Fan On
  • Color: Premier White
  • Mounting: Vertical Mount
  • Temperature Control Mode Selections: “A” for Ambient Air, “F” for Floor, “AF” for Ambient & Floor.
  • Temperatures Displayed: Indoor, Set Point, Outdoor
  • Setting Temperature Range (F): 40 F to 100 F
  • Floor Temperature Limit Range (AF Model) (F): 40 F to 100 F
  • Differential Temperature (F): ± 1 F
  • Outdoor Temperature Display Range (F): -58 F to 149 F
  • Temperature Display Interval (F): +/- 1.0 F
  • Temperature Range, Storage (F): -20 F to 130 F
  • Operating Humidity Range (% RH): 5 to 90% RH, non-condensing
  • Sensor Element: Thermistor
  • Sensors (Floor) Used: 10 kilohm NTC thermistor at 25 C (77 F) +/- 0.5F (+/-0.3C) up to 500 ft (150 M) using 18 AWG or larger wire, beta=3892. Lead Length: 10 ft. (3050 mm).
  • Floor Sensor Temperature Rating (F): -58F to 230F
  • Electrical Connections: Wire-clamp screw terminals
  • Terminal Designations: TH, TH, Sensor, Sensor
  • Dimensions (in.): 3.0 in. wide x 4.9 in. high x 1.0 in. deep
  • Weight (lb): .3 lbs
  • Tradeline Value: Tradeline
  • Ambient Temperature Range (F): 32 F to 158 F
Back To Top