skip to Main Content

Honeywell R7848B1014 Flame Amplifier

SKU: c9c354f12c50 Category:
Contact us for pricing
We can match or beat most prices.
(610) 876-2000

Description

Overview
Solid state plug-in amplifiers that respond to flame detector inputs to indicate the presence of flame when used with 7800 SERIES relay modules.
Features
Flame failure response time of 0.8 or 3.0 seconds.
Flame signal strength ranges from 0.0 to 5.0 Vdc.
Plug into 7800 relay module through printed circuit board edge connector keyed for proper orientation.
Flame signal test jacks to measure amplifier flame signal voltage.
Color-coded labels identify flame detection type. Dynamic Self-Check Amplifier test the detectors and all electronic components in the flame detection system 7800 SERIES relay module locks out on safety shutdown with flame detection system failure.
Compatible with existing Honeywell flame detectors (order separately).
Product Specifications
CommentsColor: RedApprovals, Underwriters Laboratories Inc.Listed: File No. MP268, Guide No. MCCZApprovals, CSACertified: File No. LR95329-3Customer SpecialCleaver BrooksOperating Temperature Range (F)-40 F to +140 FOperating Temperature Range (C)-40 C to +60 CFlame Failure Response Time (sec)2.0 sec or 3.0 secApprovals, Control Safety DevicesN/SApprovals, Swiss REAcceptableApprovals, Factory MutualApproved: Report No. 1V9A0.AFTypeInfraredSelf CheckingAmpli-CheckUse With Primary Safety Control7800 SERIES Relay ModulesUse With Flame SensorGas, oil, coal: Infrared ( lead sulfide) C7015

Back To Top