Honeywell, Inc. V4055A1296 On-Off Fluid Power Gas
Description
Maximum Safe Operating Pressure (psi)5 psiMaximum Safe Operating Pressure (kPa)34 kPaTemperature Range (F)-40 F to +150 FTemperature Range (C)-40 C to +66 CUsed WithV5055;V5097 Gas ValvesElectrical Ratings120 VacFrequency60 HzApprovals, Underwriters Laboratories Inc.When used with V5055A-E (3/4 to 4 in.) or V5097A-E (3/4 to 3 in.): Listed, File No. MH1639 Guide No. YIOZApprovals, Canadian Standards AssociationWhen used with V5055 and V5097: Certified General listed File No. 158158, Class 3371 for USA and CanadaApprovals, Swiss REWhen used with V5055 or V5097: AcceptableApprovals, Factory MutualWhen used with the V5055A,B or V5097A,B: Approved, Report Nos. 20698, 20835, 21172, and 24061TimingOpening– 13 sec; Closing– < 1 secInternal Auxiliary SwitchYes – adjusted to 90% strokeAuxiliary Switch Ratings120 Vac– 9.8 AFL, 58.8 ALR, 1/2 hp; 240 Vac– 4.9 AFL, 29.4 ALR, 1/2 hp