Honeywell, Inc. M9484E1017 Modutrol IV Motor
Description
Overview
Reversing, proportional motors used to drive burner firing rate valves, dampers or auxiliary equipment. Replace M941A,C,D motors.
Features
Designed for flame safeguard applications in commercial/industrial oil or gas burner system.
Vibration resistant electronic drive circuit.
Regulated by three-wire proportional controller.
Stroke is field-adjustable to 90 or 160 degrees.
Product Specifications
Dimensions (in.)6.45 in high x 5.5 in wide x 7.3 in deepDimensions (mm)164 mm high x 140 mm wide x 185 mm deepItem TypeProductFrequency50 Hz; 60 HzApprovals, Underwriters Laboratories Inc.Listed: File No. E4436, Guide No. XAPX for USA and CanadaSupply Voltage24 VacPower Consumption15 WTiming90 degree stroke– 30 seconds, 160 degree stroke– 60 secondsAmbient Temperature Range (F)-40 F to +150 FAmbient Temperature Range (C)-40 C to +66 CInput Signal135 ohmInternal Auxiliary Switch1Auxiliary Switch Ratings120 Vac– 7.2 AFL, 43.2 ALR, 40 VA pilot duty opposite contact; At 240 Vac– 3.6 AFL, 21.6 ALR, 40 VA pilot duty opposite contactStrokeAdjustable; 90 to 160 degrees, SymmetricalShaft Dimensions (in.)double-ended, 3/8 in. squareTorque Rating (lb-in.)150 lb-in.Torque Rating (Nm)17 NmAdditional Torque Ratings (lb-in.)Breakaway– 300 lb-in.Additional Torque Ratings (Nm)Breakaway– 34.0 NmAuxiliary Switch Setting1 degreeFactory Stroke Setting90 degreesShaft Dimensions (mm)double-ended, 9.5 mm squareDeadweight Load on ShaftEither End– 200 lb (300 lb combined power and auxiliary shafts); 90.8 kg (136 kg combined power and auxiliary shafts);

