skip to Main Content

Honeywell AQ15100B Aquatrol® boiler reset module used with AQ251 series

SKU: a53782c2c35d Category:
Contact us for pricing
We can match or beat most prices.
(610) 876-2000

Description

Replacement control modules for AQ2000 panels

Product Specifications

Application
Replacement boiler control module for AQ251
Dimensions (in.)
7 1/8 in wide x 2 1/2 in high x 4 1/4 in deep
Dimensions (mm)
18 cm wide x 94 cm high x 10.09 cm deep
Weight (lb)
1.0 lbs
Weight (kg)
0.5 kg
Approvals, Canadian Standards Association
CSA C/US Certified to CSA and UL Standards, File No. LR76030
Setback Program
7 day, up to 2 setback periods/day.
User Interface
LCD Display and a 7 button Key Pad
Boiler Control Temperature (F)
Supply–Max: OFF, 120F to 225 F; Min: OFF, 59F to 180F; Differential–2 F to 41 F or Auto (minimum 2 minutes on time)
Boiler Control Temperature (C)
Supply–Max: OFF, 49C to 107 C; Min: OFF, 15C to 82C; Differential–1 C to 23 C or Auto (minimum 2 minutes on time)
Boiler Design Temperature (F)
80F to 210F
Boiler Design Temperature (C)
26C to 99C
Outdoor Low Design Control Temperature (F)
-60F to 32F
Outdoor Low Design Control Temperature (C)
-51 C to 0 C
Return Min. Control Temperature (F)
80 F to 180 F
Return Min. Control Temperature (C)
27C to 82C
Boiler Heat Post Purge
Off, 10 seconds to 30 minutes (factory default is 30 seconds)
Pump/Valve exercise
30 seconds per 2 weeks of space heating inactivity
R-C Input (on Control and Zoning Modules)
24 Vac Class II (input on Control and Zoning Modules)
Demand Input
Heat Demand (Thermostat R-W), Auxiliary Demand, and DHW Demand–External dry contacts connection only
B-B Communication Bus Terminals
Low voltage, Class II, 2-wire polarity-insensitive, digital communicating link to other Control or Zoning modules.
Output Ratings
Boiler (T-T)– 24 Vac, 0.5A, 12VA; Auxiliary Low Voltage– 24 Vac, 0.5A, 12VA
Mixing Valve Modulating Output
0-10 Vdc to boiler
Electrical Connections
Wire-clamp screw terminals, Maximum 2 x 14 AWG each on line voltage terminals
Operating Humidity Range (% RH)
5 to 90% RH, non-condensing
WWSD (Warm Weather Shut Down) Temperature (F)
Off, 35 F to 100 F
WWSD (Warm Weather Shut Down) Temperature (C)
Off, 1 C to 38 C
Temperature Ratings (C)
Panel–0 C to 55 C
Temperature Ratings (F)
Panel–32 F to 130 F