Skip to content

Honeywell R7824C1002 Dynamic self check flame

SKU: fcd819f09d81 Category:

Description

Overview
Solid state plug-in amplifiers that respond to flame detector inputs to indicate the presence of flame when used with 7800 SERIES relay modules.
Features
Flame failure response time of 0.8 or 3.0 seconds (1.0 or 2.0 for CE approved devices).
Flame signal strength ranges from 0.0 to 5.0 Vdc.
Plug into 7800 relay module through printed circuit board edge connector keyed for proper orientation.
Flame signal test jacks to measure amplifier flame signal voltage.
Color-coded labels identify flame detection type.
-Dynamic Self-Check Amplifier test the detectors and all electronic components in the flame detection system.
-Ampli-check tests the amplifier and 7800 SERIES Relay.
-None (standard) is just tested at normal system startup.
7800 SERIES relay module locks out on safety shutdown with flame detection system failure.
Compatible with existing Honeywell flame detectors (order separately).
Product Specifications
CommentsColor: GreenApprovals, Underwriters Laboratories Inc.Listed: File No. MP268, Guide No. MCCZApprovals, CSACertified: File No. LR95329-3Customer SpecialN/SFlame Failure Response Time (sec)3.0 secApprovals, Control Safety DevicesN/SApprovals, Swiss REAcceptableApprovals, Factory MutualApproved: Report No. 1V9A0.AFTypeUltravioletSelf CheckingDynamic Self-CheckUse With Primary Safety ControlRM7824Use With Flame SensorC7024E, F Flame Detector