Skip to content

Honeywell V4062D1002 – Hi/Lo/Off Fluid Power Gas Valve Actuator

SKU: 687a8f61ec0f Category:

Description

Overview
Use with V5055 or V5097 Gas Valves to control gas supply for commercial and industrial burners. Valve opens to low fire position when power is applied; valve opens all the way on demand.
Features
Provide final safety shutoff service when used with V5055 or V5097 gas valve.
One-second maximum closing time.
Continuously displays the valve position with a red indicator when open and a yellow indicator when closed.
Mount in any position directly to valve bonnet with three setscrews.
Provide final safety shutoff service when used with V5055 or V5097 Gas Valves.
Product Specifications
Maximum Safe Operating Pressure (psi)5 psiMaximum Safe Operating Pressure (kPa)34 kPaTemperature Range (F)-40 F to +150 FTemperature Range (C)-40 C to +66 CIncludesDamper ShaftUsed WithV5034; V5055; V5097; VE5000Electrical Ratings120 VacFrequency60 HzApprovals, Underwriters Laboratories Inc.When used with V5055A-E (3/4 to 4 in.) or V5097A-E (3/4 to 3 in.): Listed, File No. MH1639 Guide No. YIOZApprovals, Canadian Standards AssociationWhen used with V5055 and V5097: Certified General listed File No. 158158, Class 3371 for USA and CanadaContact RatingsProof of Closure (Factory Mutual) Switch– 9.8 AFL, 58.8 ALR, 1/2 hp; 4.9 AFL, 29.4 ALR, 1/2 hpApprovals, Swiss REWhen used with V5055 or V5097: AcceptableTimingOpening– 26 sec; Closing– < 1 secInternal Auxiliary SwitchNo

Back To Top